1、《建筑防煙排煙系統(tǒng)技術(shù)標(biāo)準(zhǔn)》對(duì)風(fēng)管耐火極限的規(guī)定:
1. Fire resistance limit of air duct specified in Technical Standard for Building Smoke Control and Smoke Extraction System:
(1)排煙風(fēng)管
(1) Smoke exhaust duct
(2)消防通風(fēng)管道安裝加壓送風(fēng)風(fēng)管
(2) Installation of pressurized air supply duct for fire ventilation duct
(3)送風(fēng)風(fēng)管
(3) Air supply duct
2、《建筑設(shè)計(jì)防火規(guī)范》對(duì)風(fēng)管耐火極限的規(guī)定:
2. Fire resistance limit of air duct specified in Code for Fire Protection Design of Buildings:
風(fēng)管越過(guò)耐火極限、樓板和防火墻時(shí),穿越處風(fēng)管里的排煙防火閥、防火閥兩邊各2.0m范圍里的風(fēng)管應(yīng)采用防火風(fēng)管或風(fēng)管表面應(yīng)采用防火保障措施,且耐火極限不可小于該防火分隔體的耐火極限。
When the air duct crosses the fire resistance limit, floor slab and firewall, the smoke exhaust fire damper in the air duct at the crossing and the air duct within 2.0m on both sides of the fire damper shall adopt fire resistant air duct or the air duct surface shall adopt fire protection measures, and the fire resistance limit shall not be less than the fire resistance limit of the fire compartment.

(一般狀況,耐火極限耐火極限2.0h;樓板耐火極限1.5h;防火墻耐火極限3.0h。)
(In general, the fire endurance is 2.0h; the fire endurance of floor slab is 1.5h; the fire endurance of firewall is 3.0h.)
3、《建筑防煙排煙系統(tǒng)技術(shù)標(biāo)準(zhǔn)》對(duì)風(fēng)管隔熱的規(guī)定:
3. The Technical Standard for Building Smoke Control and Smoke Exhaust System specifies the thermal insulation of air duct:
當(dāng)?shù)蹴攦?nèi)有可燃物時(shí),吊頂里的排煙管道應(yīng)選用不燃材料開展隔熱,并應(yīng)與可燃物維持不小于150mm的間距。
When there are combustibles in the ceiling, the smoke exhaust pipe in the ceiling shall be insulated with incombustible materials, and the distance between the pipe and the combustibles shall not be less than 150mm.
注:排煙風(fēng)管設(shè)定隔熱的目的是避免高溫?zé)焿m點(diǎn)燃吊頂里的可燃物。車庫(kù)無(wú)吊頂,且都是機(jī)電管道,無(wú)可燃物,從隔熱規(guī)定來(lái)看,車庫(kù)排煙風(fēng)管無(wú)需設(shè)定隔熱對(duì)策。當(dāng)?shù)蹴攦?nèi)無(wú)可燃物時(shí),也無(wú)需設(shè)定隔熱對(duì)策。
Note: The purpose of setting thermal insulation for smoke exhaust duct is to prevent high-temperature smoke and dust from igniting combustibles in the ceiling. The garage has no suspended ceiling, and is all mechanical and electrical pipes, free of combustibles. From the perspective of thermal insulation regulations, the garage smoke exhaust duct does not need to set thermal insulation measures. When there are no combustibles in the ceiling, there is no need to set thermal insulation measures.
螺旋通風(fēng)管道廠家隔熱和耐火極限是兩個(gè)不同的概念!
Thermal insulation and fire resistance limit of spiral ventilation duct are two different concepts!
4、耐火極限定義
4. Definition of fire endurance
在規(guī)范防火試驗(yàn)條件下,建筑構(gòu)件、配件或構(gòu)造從受到火的作用時(shí)起,至喪失承載力、完整性或隔熱性時(shí)止常用的時(shí)間,用小時(shí)表示。
Under the specified fire test conditions, the common time from the time when building components, fittings or structures are exposed to fire to the time when they lose their bearing capacity, integrity or thermal insulation is expressed in hours.
通風(fēng)管道加工安裝的耐火極限包含風(fēng)管的防火完整性和風(fēng)管的防火隔熱性,二者必須同時(shí)滿足。與結(jié)構(gòu)梁、柱子、承重梁不同的是,風(fēng)管無(wú)需滿足防火承載力。
The fire endurance of the processing and installation of the ventilation duct includes the fire integrity of the air duct and the fire insulation of the air duct, both of which must be met at the same time. Unlike structural beams, columns and load-bearing beams, air ducts do not need to meet the fire resistance bearing capacity.
The above is a detailed introduction to the ventilation pipes in Jinan. I hope it will be helpful to you. If you have any questions, please contact us. We will provide services for you with our attitude http://www.lyqhjxzl.com
上一篇:通風(fēng)管道伸縮節(jié)分類及使用要求
下一篇:不銹鋼通風(fēng)管道加工的性能特點(diǎn)概述